Addr. Parameter C Setting Options Default Setting
_:13981:115 Tap changer:Highest tap
position
-64 to 64 15
General
_:14011:1 90V V.contr.2w:Mode
•
off
•
on
•
test
on
_:14011:101 90V V.contr.2w:Oper-
ating mode
•
Manual
•
Auto
Manual
Control
_:14011:107 90V V.contr.2w:Check
switching authority
•
no
•
yes
yes
_:14011:109 90V V.contr.2w:Control
model
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:14011:110 90V V.contr.2w:SBO
time-out
0.01 s to 1800.00 s 30.00 s
_:14011:111 90V V.contr.2w:Feed-
back monitoring time
0.01 s to 1800.00 s 10.00 s
Voltage Control
_:14011:156 90V V.contr.2w:Number
of target voltage
•
1
•
2
•
3
•
4
1
_:14011:112 90V V.contr.2w:Target
voltage 1
10.000 V to 340.000 V 110.000 V
_:14011:157 90V V.contr.2w:Target
voltage 2
10.000 V to 340.000 V 110.000 V
_:14011:158 90V V.contr.2w:Target
voltage 3
10.000 V to 340.000 V 110.000 V
_:14011:159 90V V.contr.2w:Target
voltage 4
10.000 V to 340.000 V 110.000 V
_:14011:113 90V V.contr.2w:Band-
width
0.2 % to 10.0 % 1.0 %
_:14011:114 90V V.contr.2w:T1 char-
acteristic
•
Linear
•
Inverse
Linear
_:14011:115 90V V.contr.2w:T1 delay 5 s to 600 s 40 s
_:14011:116 90V V.contr.2w:T1
Inverse Min
5 s to 100 s 5 s
_:14011:117 90V V.contr.2w:T2 delay 0 s to 100 s 5 s
_:14011:118 90V V.contr.2w:Fast step
up
•
off
•
on
off
_:14011:119 90V V.contr.2w:Fast step
up limit
-50.0 % to 0.0 % -6.0 %
_:14011:120 90V V.contr.2w:Fast step
up T delay
0.0 s to 10.0 s 2.0 s
_:14011:121 90V V.contr.2w:Fast step
down
•
off
•
on
on
_:14011:122 90V V.contr.2w:Fast step
down limit
0.0 % to 50.0 % 6.0 %
_:14011:123 90V V.contr.2w:Fast step
down T delay
0.0 s to 10.0 s 0.0 s
Control Functions
8.9 Voltage Controller
SIPROTEC 5, Overcurrent Protection, Manual 1223
C53000-G5040-C017-8, Edition 07.2017