Addr. Parameter C Setting Options Default Setting
_:14011:124 90V V.contr.2w:Function
monitoring
0 min to 120 min 15 min
_:14011:155 90V V.contr.2w:Regulate
with T2 at start
off
on
on
_:14011:160 90V V.contr.2w:Set
point mode active
off
on
on
Line drop comp.
_:14011:125 90V V.contr.2w:Line
drop compensation
off
LDC-Z
LDC-XandR
off
_:14011:126 90V V.contr.2w:Target
voltage rising
0.0 % to 20.0 % 4.0 %
_:14011:127 90V V.contr.2w:Max
load current
0.0 % to 500.0 % 100.0 %
_:14011:153 90V V.contr.2w:R line 0.0 Ω to 30.0 Ω 0.0 Ω
_:14011:154 90V V.contr.2w:X line -30.0 Ω to 30.0 Ω 0.0 Ω
Limiting
_:14011:102 90V V.contr.2w:Lower
tap-position limit
-128 to 127 1
_:14011:103 90V V.contr.2w:Higher
tap-position limit
-128 to 127 15
_:14011:128 90V V.contr.2w:Vmin
limiting
off
on
on
_:14011:129 90V V.contr.2w:Vmin
threshold
10.000 V to 340.000 V 105.000 V
_:14011:130 90V V.contr.2w:Vmin
time delay
0 s to 20 s 10 s
_:14011:131 90V V.contr.2w:Vmax
limiting
off
on
on
_:14011:132 90V V.contr.2w:Vmax
threshold
10.000 V to 340.000 V 115.000 V
_:14011:133 90V V.contr.2w:Vmax
time delay
0 s to 20 s 10 s
Blocking
_:14011:134 90V V.contr.2w:Blocking
behavior
Auto
Auto-Manual
Auto-Manual
_:14011:135 90V V.contr.2w:V<
Blocking
off
on
on
_:14011:136 90V V.contr.2w:V<
Threshold
10.000 V to 340.000 V 90.000 V
_:14011:137 90V V.contr.2w:V< Time
delay
0 s to 20 s 0 s
_:14011:138 90V V.contr.2w:I>
Blocking
off
on
on
_:14011:139 90V V.contr.2w:I>
Threshold
10 % to 500 % 150 %
_:14011:140 90V V.contr.2w:I> Time
delay
0 s to 20 s 0 s
_:14011:141 90V V.contr.2w:I<
Blocking
off
on
off
Control Functions
8.9 Voltage Controller
1224 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017