Addr. Parameter C Setting Options Default Setting
_:14011:142 90V V.contr.2w:I<
Threshold
3 % to 100 % 10 %
_:14011:143 90V V.contr.2w:I< Time
delay
0 s to 20 s 10 s
Three-Winding Transformer
Addr. Parameter C Setting Options Default Setting
Winding 1
_:2311:101 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:103 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Winding 2
_:2311:102 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:104 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
_:2311:106 General:Rated apparent
power
-1.00 MVA to -1.00 MVA 0.00 MVA
Tap changer
_:13981:111 Tap changer:Maximum
output time
0.02 s to 1800.00 s 1.50 s
_:13981:112 Tap changer:Supervision
behavior
off
warning
alarm block
alarm block
_:13981:113 Tap changer:Motor
supervision time
5 s to 100 s 10 s
_:13981:116 Tap changer:Highest tap
changer pos.
Lowest voltage tap
Highest voltage tap
Lowest voltage
tap
_:13981:114 Tap changer:Lowest tap
position
-64 to 64 1
_:13981:115 Tap changer:Highest tap
position
-64 to 64 15
General
_:15601:1 90V V.contr.3w:Mode
off
on
test
on
_:15601:101 90V V.contr.3w:Oper-
ating mode
Manual
Auto
Manual
_:15601:157 90V V.contr.3w:Winding
selection
Winding 1
Winding 2
WithMaxLoad
Winding 1
Control
_:15601:107 90V V.contr.3w:Check
switching authority
no
yes
yes
_:15601:109 90V V.contr.3w:Control
model
direct w. normal secur.
SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
SBO w. enh.
security
_:15601:110 90V V.contr.3w:SBO
time-out
0.01 s to 1800.00 s 30.00 s
_:15601:111 90V V.contr.3w:Feed-
back monitoring time
0.01 s to 1800.00 s 10.00 s
Control Functions
8.9 Voltage Controller
SIPROTEC 5, Overcurrent Protection, Manual 1225
C53000-G5040-C017-8, Edition 07.2017