Addr. Parameter C Setting Options Default Setting
CT 2
_:3842:103 CT 2:Magnitude correc-
tion
0.010 to 10.000 1.000
_:3842:117 CT 2:Phase
I A
I B
I C
IN
INsens
Ix
_:3842:116 CT 2:Sequence number
device
1 to 2147483647 2147483647
CT 3
_:3843:103 CT 3:Magnitude correc-
tion
0.010 to 10.000 1.000
_:3843:117 CT 3:Phase
I A
I B
I C
IN
INsens
Ix
_:3843:116 CT 3:Sequence number
device
1 to 2147483647 2147483647
CT 4
_:3844:103 CT 4:Magnitude correc-
tion
0.010 to 10.000 1.000
_:3844:117 CT 4:Phase
I A
I B
I C
IN
INsens
Ix
_:3844:116 CT 4:Sequence number
device
1 to 2147483647 2147483647
Brk.wire det.
_:5581:1 Brk.wire det.:Mode
off
on
test
off
Supv. balan. I
_:2491:1 Supv. balan. I:Mode
off
on
test
off
_:2491:101 Supv. balan. I:Release
threshold
1 A @ 100 Irated 0.030 A to 35.000 A 0.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 2.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 2.500 A
_:2491:102 Supv. balan. I:Threshold
min/max
0.10 to 0.95 0.50
_:2491:6 Supv. balan. I:Delay
supervision alarm
0.00 s to 100.00 s 5.00 s
Protection and Automation Functions
6.1 Power-System Data
314 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017