Addr. Parameter C Setting Options Default Setting
Supv. ph.seq.I
_:2551:1 Supv. ph.seq.I:Mode
off
on
test
off
_:2551:6 Supv. ph.seq.I:Delay
supervision alarm
0.00 s to 100.00 s 5.00 s
Supv. sum I
_:2431:1 Supv. sum I:Mode
off
on
test
off
_:2431:102 Supv. sum I:Threshold 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2431:101 Supv. sum I:Slope factor 0.00 to 0.95 0.10
_:2431:6 Supv. sum I:Delay super-
vision alarm
0.00 s to 100.00 s 5.00 s
Supv.ADC sum I
_:2401:1 Supv.ADC sum I:Mode
off
on
test
off
Measuring Point I-1ph
Addr.
Parameter C Setting Options Default Setting
General
_:2311:101 General:Rated primary
current
1.0 A to 100 000.0 A 1000.0 A
_:2311:102 General:Rated secondary
current
1 A
5 A
1 A
_:2311:103 General:Current range
1.6 x IR
100 x IR
50 x IR
100 x IR
_:2311:104 General:Internal CT type
CT protection
CT measurement
CT Process bus
CT protection
_:2311:116 General:Term. 1,3,5,7 in
dir. of obj.
no
yes
yes
_:2311:105 General:Tracking
inactive
active
inactive
_:2311:130 General:Measuring-point
ID
0 to 100 0
CT 1
_:3841:103 CT 1:Magnitude correc-
tion
0.010 to 10.000 1.000
Protection and Automation Functions
6.1 Power-System Data
SIPROTEC 5, Overcurrent Protection, Manual 315
C53000-G5040-C017-8, Edition 07.2017