9410 series Maintenance
WARNING
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Do not use this device for critical control or protection applications where human or
equipment safety relies on the operation of the control circuit.
Loading firmware or template onto your meter clears the meter’s recorded data.
NOTICE
DATA LOSS
Failure to follow these instructions can result in data loss.
Ensure that all important data has been recorded before uploading firmware or a
template to your device.
1. Obtain the meter firmware (.UPG) and framework (.DCF) that you want to load
onto your meter. Save the files where they can be accessed by the computer
running ION Setup.
2. Start ION Setup.
3. Open the Setup Assistant for your meter.
4. Select the Template screen.
5. Click the Firmware Upgrade tab, then click Upgrade. Enter your meter’s
password (if prompted) and click OK.
NOTE: If you want to retain customized meter template settings, other than
those listed in the Template Paste Options dialog box (see Step 8), click on
the Save to PC tab and click Save. Save your template as a .DCF file. Select
this file in Step 7 instead of the file obtained from the website.
6. Navigate to the meter firmware (.UPG) file and click Open. Enter your ION Setup
password when prompted and click OK.
7. Navigate to the meter framework (.DCF) file and click OK.
The Template Paste Options dialog box appears.
8. Select the check boxes for the settings you want to retain (not overwrite) and click
OK.
A dialog box describes the template upload and firmware upgrade progress, verifies
the firmware, and finishes with an overview stating whether the firmware and
framework were successfully uploaded onto your meter.
Post-requisite:
After upgrading your meter’s firmware or template, make sure that the meter’s
settings, either for existing functionality or new features, are appropriate for your
system.
Loading option module firmware using ION Setup
You can upload firmware to your meter’s option modules using ION Setup over an
Ethernet connection.