Communications 9410 series
3. Configure your meter’s SNMP parameters by selecting the parameter value.
Parameter Range Description
Enable SNMP . Yes/no Enables or disables SNMP on your meter.
SNMP Port Number 161 (default) Enter your meter’s SNMP port number.
System contact
Enter the name of your SNMP system administrator.
System name
Enter a descriptive name for your meter.
System location
Enter your meter’s location.
Read-only Community Name
Enter the community string used for SNMP get (read-only) requests.
Read-write Community Name
Enter the community string used for SNMP set (read/write) requests. NOTE:
You can use the read/write community string for SNMP get (read-only)
requests.
Enable SNMP Traps Enable/disable Enables or disables SNMP trapping on your meter.
Enable High Priority Alarms Yes/no Enables trapping of events that create high priority alarms.
Enable Med Priority Alarms Yes/no Enables trapping of events that create medium priority alarms.
Enable Low Priority Alarms Yes/no Enables trapping of events that create low priority alarms.
Report Buffer Size 1 - 30 Enter the maximum number of trap messages to be stored before the trap
messages are sent. Traps are sent when the number of trap messages is
equal to or greater than this value.
Report Hold Time 1 - 300 seconds Enter the maximum duration for trap messages to be held. Trap messages
are sent when the time after a trap event has occurred is equal to or greater
than this value.
Trap Rcvr1 Addr -
Trap Rcvr4 Addr
Enter up to four trap receiver IP addresses, where trap messages will be
sent.
4. Click Apply to configure the meter’s SNMP parameters.
SNMP implementation
MIB files
Your meter is compliant with MIB-II as defined by the standard MIB file RFC 1213.
SNMP requires that you load your meter’s ION MIB file (available for download from
www.usa.siemens.com/pds) into the NMS.
You must install RFC 1213, which is required to read basic network information for the
meter (for example, TCP/IP traffic or number of packets received), if it is not included
with your SNMP manager software.
Community strings
A community string is a text string which acts to help authenticate requests from the
NMS to your meter.
There are two community strings on your meter:
Read Only Community: this community string is used by SNMP get (read-only)
requests. The read only community string’s initial factory-set value is public.
Read Write Community: this community string is used by SNMP set (read/write)
requests. The read write community string’s initial factory-set value is private.
NOTE: You can also use the read write community string for SNMP get (read-only)
requests.