Establishing the hardware needed
29
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
10 Establishing the hardware needed
The key system data must be known in order to determine the hardware needed:
1. Define number and type of detector lines
Depending on:
Detector series
Number of detectors, input and output modules
Building structure
2. Define number and type of fire controls
Depending on:
The fire protection installations to be controlled
Location of contacts (central or decentralized)
Contact type of the individual contacts (250 V AC/10 A or 30 V DC/1 A)
3. Define number and type of operating units
Depending on:
Operating concept
Language of operating front
Parallel displays, fire brigade operating units
4. Options
Depending on:
Printer interface and printer
PSA/pager interface
Remote transmission device
Gateway, etc.
5. Define capacity of emergency power battery
Depending on:
Total quiescent current
Emergency power needed for operating period (country-specific)
Type of remote transmission
6. Define housing type
Depending on:
Number and type of plug-in modules
Optional devices needed
Number and type of sets of batteries
7. Produce configuration sheet(s) (see page 113)
Select sheets corresponding to configuration
Complete everything

Table of Contents

Other manuals for Siemens AlgoRex CS1140

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens AlgoRex CS1140 and is the answer not in the manual?

Siemens AlgoRex CS1140 Specifications

General IconGeneral
BrandSiemens
ModelAlgoRex CS1140
CategorySecurity Sensors
LanguageEnglish

Related product manuals