PSA interface
94
Building Technologies 008725_h_en_--
Fire Safety & Security Products 06.2011
34 PSA interface
34.1 Features
The PSA interface board K3I090 can be used universally and serves to analyze
the data transmitted by a control panel to its printer output and to transfer this to
a PSA or pager system in ESPA 4.4.4 format.
The optional printer is connected to the PSA interface board. If there is a printer
available, the data is forwarded straight to the printer. The interposed PSA inter-
face board is not visible to the control panel and printer.
The PSA interface board analyzes the print data for character strings at a particu-
lar position following defined rules. The rules are saved in the PSA interface
board. If a string of characters matches, the content of the printer message is
prepared for display on the pager or forwarded unchanged to the PSA.