46
Fire & Security Products
Siemens Building Technologies Group
01.1999
Input module (triple) DC1157/DC1157-AA
Note:
If, after being booted, the system is set in ”Localization” mode, (activation, insertion),
the D-Bus addresses for the DC1157 may be redistributed (lower D-Bus addresses).
The consequence is that during or after commissioning the DC1157s no longer ap-
pear.
Action:
– Do not boot the system and then switch to ”localization” mode.
– if possible first commission the DC1157 (low D-Bus address) or
– commission the DC1157 at the end
Procedure for the first commissioning
The physical devices used are each linked to a logical element. (In the following ex-
ample all three inputs are used.)
Permissible element types:
Digital element (’EL digital’)
Digital detector element (’EL digital det.’)
– Digital manual call point element (’EL digital man.’)
Command element (’EL command’)
– Output element with confirmation (’EL out 2’) only confirmation path
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning
2. Using the commissioning list, select a DC1157 input module in the localization struc-
ture and the first corresponding element in the logical structure, e.g. a digital element
(’EL digital’).
Reference:
Localization index of the address allocation or
device identification
Select
DC1157
Select 1st element
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 201 (1601,426)
>001.001.001.001/001: DO1151 4 (1501,427)
>001.001.001.002/001: DO1151 2 AI (1501,428)
>001.001.001.003/001: DO1151 (1501,429)
>001.001.001.004/001: DO1151 (1501,430)
001.001.002/ZO multi/2/laboratory 203 (1602,445)
>001.001.002.001/004: DOT1151 6 Window (1501,446)
>001.001.002.002/004: DOT1151 5 Door (1501,447)
3. Link nodes together
Function Structure Link
CAUTION:
Because the three input sections of a DC1157 are represented as three individual
devices in the physical structure and no common reference is available showing affil-
iation to the same DC1157, the SWE11 can not automatically transfer the localization
data to all three devices. The localization data must, therefore, be allocated individ-
ually to all three elements linked to the physical devices .
After the first linking with an element the DC1157 is identified as localized no prefix.
4. Using the commissioning list, select the second element corresponding to the
DC1157 in the logical structure