EasyManua.ls Logo

Siemens Cerberus CS1140 - Page 51

Siemens Cerberus CS1140
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
e1249d2
47
Fire & Security Products
Siemens Building Technologies Group
01.1999
DC1157 represented
in the physical structure
by 3 separate devices
(’DE DS11 in’)
Localization
structure
’104: DC1157’
Function unit
DC1157 represented in
the localization structure by
one device
Station
e.g. ’EL digital’
Links
’FU DS11i’
Zone Zone Zone
Logical
structure
Physical
structure
Select DC1157
identified as localized, because
an element has already been allo-
cated !
Select second element
AlgoWorks 00ST0245 09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB (1801,1)
001.001/SE fire/2nd floor west (1701,425)
001.001.001/ZO single/1/laboratory 201 (1601,426)
>001.001.001.001/001: DO1151 4 (1501,427)
>001.001.001.002/001: DO1151 2 AI (1501,428)
>001.001.001.003/001: DO1151 (1501,429)
>001.001.001.004/001: DO1151 (1501,430)
001.001.002/ZO multi/2/laboratory 203 (1602,445)
>001.001.002.001/004: DOT1151 6 Window (1501,446)
>001.001.002.002/004: DOT1151 5 Door (1501,447)
5. Link nodes together
Function Structure Link
6. Repeat steps 4 and 5 for the third of the elements corresponding to the DC1157
Procedure if some of the inputs of the same DC1157 are used only after commis-
sioning has already been carried out
1. Generate and link new logical elements and physical devices
2. In the physical structure open nodes of a device already in operation
3. Note D-Bus addresses and device ID
4. Enter the above value in all newly generated devices
Input / output module DC1192
Possible uses
The DC1192 input / output modules can either be used as an input module for the opera-
tion of a collective line (DC1192c) or as an output module to activate monitored alarm
devices (DC1192h).
Procedure when used as an input module
1. Switch over from the physical structure to the localization structure
Function Loc. Commissioning