Technical Instructions
LV5-1000
Menu Path Parameter Default Range Description
51.1
52.2
52.4
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
LMV
Curr Flow Rate (U)
Current flow rate for the fuel being fired. Gas = cubic meters or cubic feet per hour. Oil =
liters or gallons per hour.
x x
Volume Gas (U) Totalized volume of gas used since the last reset.
x x
Volume Oil (U) T
otalized volume of oil used since the last reset.
x x
Volume Gas R (U) Resets the totalized volume of gas.
x x
Volume Oil R (U) Resets the totalized volume of oil.
x x
Reset DateGas (U) This displays the date of the last reset for gas.
x x
Reset DateOil (U) This displays the date of the last reset for oil.
x x
ServicePassword (O) 9876
3 to 8
characters
The service level password can be changed here.
x x x
OEM Password (O) START
4 to 8
characters
The OEM level password can be changed here.
x x x
Updating BurnerID (O)** Not Set
4 to 15
characters
Burner ID must be set here. Typically the burner / boiler serial number is used. Serves as an
identifier for the parameter set.
x x x
Date (U) This displays the date of the last backup.
x x x
TimeOfDay (U) This displays the time of day of the last backup.
x x x
BU included? (U) This states if the basic unit (LMV5) was included in the last backup.
x x x
AZL included? (U) This states if the AZL was included in the last backup.
x x x
LC included? (U) This states if the LC (load controller) was included in the last backup.
x x
x
ACT1 included? (U) This states if the Act 1 (Actuator 1) was included in the last backup.
x x x
ACT2 included? (U) This states if the Act 2 (Actuator 2) was included in the last backup.
x x x
ACT3 included? (U) This states if the Act 3 (Actuator 3) was included in the last backup.
x x x
ACT4 included? (U) This states if the Act 4 (Actuator 4) was included in the last backup.
x x x
ACT5 included? (U) This states if the Act 5 (Actuator 5) was included in the last backup.
x x
ACT6 included? (U) This states if the Act 6 (Actuator 6) was included in the last backup.
x x
VSD included? (U) This states if the VSD (Variable Speed Drive) was included in the last backup.
x x
O2 included? (U) This states if the O2 module was included in the last backup.
x x
Read Only
Reset Only
Read Only
Updating>
Passwords
Updating>
ParamsBackup>
BackupInfo
Read Only
Params & Display>
Fuel Meter
Read Only
SCC Inc. Page 45 Section 3