Section 10 Page 14 SCC Inc.
VSD Module Software Update: Version 0130 to 0140
The following updates were made with L
MV52 VSD module software version 0140:
1. Opening of the release contact during shutdown can be set via parameter
ReleaseContctVSD. This enables the VSD module to use a DC break.
2. Quick shutdown of the burner when speed deviation exceeds parameter TolQuickShutdown.
VSD Module Software Update: Version 0140 to 0150
The following updates were made with L
MV5 VSD module software version 0150:
1. To avoid error code A9, diagnostic 18 (Page disrupted), statistics data are now only stored in
standby and operation.
2. In some cases, the correction offset for the speed setpoint was not reset after a safety
shutdown. This could lead to error messages. The new version eliminates this effect.
3. Internal system tests have been modified, allowing the VSD test initialized by the LMV5 to be
dropped.
4. Quick shutdown of the VSD is also affected in programming mode.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals