LMV Series
Technical Instructions
LV5-1000
Menu Path Parameter Default Range Description
51.1
52.2
52.4
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
LMV
0-90 deg15 deg
IgnitionPosVSD (S)
Sets the postpurge position of the aux2 actuator. Be aware of mechancial stops.
90 deg 0-90 deg
PrepurgePosAux3 (S)
PrepurgePosVSD (S)
Params & Display>
RatioControl>
Gas/Oil Settings>
SpecialPositions>
IgnitionPos
IgnitionPosGas or
IgnitionPosOil (S)**
0-90 deg
Not Set 0-90 deg
Not Set 0-100%
100% 0-100%
Not Set
90 deg
PrepurgePosAux1 (S)
IgnitionPosAux2 (S)
PrepurgePosAux2 (S) Sets the prepurge position of the aux2 actuator. Be aware of mechancial stops.
Params & Display>
RatioControl>
Gas/Oil Settings>
SpecialPositions>
PostpurgePos
PostpurgePosGas or
PostpurgePosOil (S)
Sets the postpurge position of the fuel actuator(s). Be aware of mechancial stops.
Params & Display>
RatioControl>
Gas/Oil Settings>
SpecialPositions>
PrepurgePos
PrepurgePosAir (S) Sets the prepurge position of the air actuator. Be aware of mechancial stops.
PostpurgePosAux3 (S) Sets the postpurge position of the aux3 actuator. Be aware of mechancial stops.
PostpurgePosVSD (S)
IgnitionPosAir (S)**
Sets ignition position of the air actuator. Setting is independent of the low fire position. Be
aware of mechancial stops.
IgnitionPosAux1 (S)
Sets the postpurge position of the air actuator. Be aware of mechancial stops.
PostpurgePosAux1 (S)
Sets ignition position of the aux1 actuator. Setting is independent of the low fire position. Be
aware of mechancial stops.
PostpurgePosAir (S)
0-90 deg
Sets ignition position of the aux2 actuator. Setting is independent of the low fire position. Be
aware of mechancial stops.
IgnitionPosAux3 (S)
Sets ignition position of the aux3 actuator. Setting is independent of the low fire position. Be
aware of mechancial stops.
Sets the postpurge position of the aux1 actuator. Be aware of mechancial stops.
PostpurgePosAux2 (S)
Sets the prepurge position of the aux3 actuator. Be aware of mechancial stops.
Sets the prepurge position of the aux1 actuator. Be aware of mechancial stops.
Sets the postpurge speed of the VSD.
0-90 deg
0-90 deg
0-90 deg
0-100%
25 deg
25 deg
25 deg
50%
x
Sets the prepurge speed of the VSD.
90 deg 0-90 deg
Not Set 0-90 deg
Not Set
Sets ignition position of the fuel actuator(s). If one fuel actuator is connected to both the gas
and oil v
alve, it can still have independent ignition positions for gas and oil. Setting is
independent of low fire. Be aware of mechancial stops.
Sets ignition speed of the VSD. Setting is independent of the low fire position.
90 deg 0-90 deg
0-90 deg
Not Set 0-90 deg
0-90 deg15 deg
x x
x x
x
x
x x x
x
x x
x x
x x x
x x
x
x
x x x
x x
x
x
x x x
x
x x x
x x x
x
x x
SCC Inc. Page 18 Section 3
HOME
HOME
P - LIST

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals