LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page13 Section5
IftheanalogsignalisdecreasedtotheminimumallowablesignalandtheblowerRPMisstillhigh,a
messagewillbedisplayedontheAZLthatstates“ControlrangelimitationVSDModule”.
Thereasonthatthestandardizationisdoneat19.5mAinsteadofat20mAistogivetheLMV52some
additional"room"toincreasetheanalogsignalforalowRPMconditionathighfire.Becausethe
standardizationisdoneat19.5mA,theanaloginputontheVFDisspannedsothat20mA=62Hz.Thisis
donesothattheblowerwillstillachievefull60Hzblowerspeedathighfireonjobswherethebloweris
justlargeeno
ugh.
NOTE:MostVFDscanbescaledtooutput400Hzormore.Consulttheblowerand/ormotor
manufacturerbeforeoverspeedingthemotorandblower,sinceblowerwheelsandmotorrotorscan
catastrophicallyfailifRPMlimitsareexceeded.
Inadditiontolimitsonhowmuchthe420mAsignalcanbecompensated,theLMV52alsohaslimitson
howfartheblowerspeedcandeviatefromthestandardizedspeedline.Thenextsectionexplainshow
theblowerspeedismonitoredwhentheburnerisinoperation.
BlowerSpeedMonitoring
Blowerspeedhasalargeimpactontheairflowdeliveredtotheburnerandthusthefuelairratio.Fuel
airratiosmustbekeptinasaferangewhileaflameispresentintheboiler.Ifthefuelairratiocannot
bekeptinasaferange,theburnermustbeshutdown.
Tohelpensurethatthebu rneriseitheroperatedatasafefuelairratioorisshutdown,theblower
speedisconstantlymonitoredwhileaflameispresentintheboiler.Thespeedismonitoredsothat
nuisanceshutdownsareeliminated,butfastshutdownswilloccurifthespeeddeviationislarge.Todo
this,theLMV52evaluatesthemagnitudeofthespeeddeviationincombin
ationwithhowlongthe
speeddeviationexists.Toaccomplishthis,threedistinctbandsandonelimitcenteredaboutthe
standardizedspeedlineareused.Thesebandsare:
1. NeutralBand‐ifthespeediswithinthisband,itisconsidered tobeOKandnoactionistaken.The
widthofthisbandis+/‐0.5%ofthestandardizedspeed.
2. LowRisk Band‐ifthespeediswithinthisband,theanalogsignaltotheVFDisadjustedtobringthe
speedbackintotheNeutralBand.IftheNeutralBandspeedcannotbeachievedin8seconds,a
lockoutwilloccur.Thewidthofthisbandis+/‐2.0%ofthestandardizedspeed.
3. OutsideLowRiskBand‐ifthespeedisoutsidetheLowRiskBandbutdoesnot exceed theHighRisk
Limit,theanalogsignaltotheVFDisadjustedtobringthespeedbackintotheLowRiskBandand
thenultimatelyintotheNeutralBand.ThewidthofthisbandvarieswiththesettingoftheHighRisk
Limit(parameterTolQuickShutdown).IftheLowRiskBand
speedcannotbeachievedin3seconds,
alockoutwilloccur.
4. HighRiskLimit(parameterTolQuickShutdown)‐ifthespeedexceedstheHighRiskLimitthreshold
formorethan1second,alockoutwilloccur.Thislimitisdeterminedbyparameter
TolQuickShutdown,whichcanbesetbytheburnerOEM.Thedefaultsettingis+/‐10%ofthe
standardizedspeed.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals