LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page25 Section6
4. InitContrO
2
controlispreparingtoengagebutisstilllocked
5. LockTLoadO
2
controlisengagedbutlocked(inprecontrol)duetoaloadchange
6. ActiveO
2
controlisactivelytrimmingbasedonsetpointandmeasuredO
2
value
7. LockTCAct‐O
2
controlisengagedbutlockedduetoanexcursionfromsetpoint
IfthestateoftheO
2
controlisshownas"locked",parameterDiagRegStatewillshowthereasonwhy.
DiagRegState
Menupath:Params&Display>O2Contr/Alarm>ProcessData
ThisparametershowsthereasonthattheO
2
controlislocked.Possiblevaluesare:
0TheloadisbelowtheloadlimitsetbyparameterO2CtrlThreshold
1Theloadcontrollerisinautotune
2TheO
2
sensorisbeingtestedforresponse(selfcheckofO
2
sensor)
3ThefuelairratioorO
2
trimcurvesarebeingprogrammed
4Themeasured%O
2
isabovetheleanlimitorbelowtherichlimit
5ThereisanerrorinthePLL52module
6Thereisanerrorintheprecontrol
UsingtheO
2
AlarmFunctionalitywithoutO
2
Trim
Aswaspreviouslymentioned,theO
2
systemcanberunindifferentmodes.Themodesaresetusing
parameterOptgMode,whichcanbefoundusingthefollowingmenupath:
Menupath:Params&Display>O2Contr/Alarm>Gas/OilSettings
Theavailableoperatingmodesare:
1. Mandeact‐deactivatesallO
2
trimandO
2
alarmfunctionality.%O
2
valuecanstillbeviewed.
2. O2Limiter‐OnlytheO
2
alarmisactive.Thismeansthatalockoutwilloccuriftheleanlimit(O2
MaxValue)isexceededforatimelongerthanwhatissetforparameterTimeO2Alarm.Likewise,a
lockoutwilloccuriftherichlimit(O
2
alarmcurve)isexceededforatimelongerthanwhatissetfor
parameterTimeO2Alarm.Notrimfunctionalityisactive.
3. O2Control‐ThesameasO2Limiter,exceptO
2
trimisnowenabled.Exceedingrichorleanlimits
willcausealockoutinthesamewayastheO2Limitermode.
4. ConAutoDeacInthismode,exceedingtherichorleanlimitswillnotcauseanimmediatelockout.
ExceedingtherichorleanlimitswillcausetheO
2
trimtobetemporarilydeactivated.Afterawaiting
timeof3timesTau,themeasured%O
2
willbereevaluated.Ifthe%O
2
ishigherthantherichalarm,
theO
2
trimwillbedeactivated.Ifthe%O
2
islowerthantherichalarm,alockoutwilloccur.TheO
2
trimcanbeautomaticallydeactivatedandreactivatedthenumberoftimesallowedbyparameter
NumMinUntilDeact.Themaximumse ttingis5.Ifmorethan5deactivationsandreactivations
occur,thentheO
2
trimmodewillbechangedto“autodeact”untiltheO
2
trimcontrolismanually
reactivated.
5. Autodeact‐indicatesthattheO
2
trimhasbeenautomaticallydeactivatedforsomereason.See
errorcodesinSection7.Donotselectthismode.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals