LMV Series
Technical Instructions
LV5-1000
Menu Path Parameter Default Range Description
51.1
52.2
52.4
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
LMV
PrepurgePt1Gas (S)
PrepurgePt1Oil (S)
PrepurgePt3Gas (S)
PrepurgePt3Oil (S)
PreIgnitionTGas (S) 2s 0.2- 63s
PreIgnitionTOil (S) 2s 0.2- 44s
MinOnTmeOilPump (S) 5s 0.2-63s
When LO w Gasp (Light Oil with Gas pilot) is selected, this is the minimum time the oil pump
can run (OUTPUT X6-02.3) before the LMV5 attempts to light the pilot, (OUTPUT X9-01.2).
Time starts in phase 22, and will hold in phase 36 until this parameter times out.
SafetyTme1Gas (O) 5s
1-MaxSafety
TGas
SafetyTme1Oil (O) 5s
1-MaxSafety
TOil
Interval1Gas (S) 2s
Interval1Oil (S) 2s
SafetyTme2Gas (O) 5s
1-MaxSafety
TGas
SafetyTme2Oil (O) 5s
1-MaxSafety
TOil
MaxSafetyTGas (O) 10s 1-10s
MaxSafetyTOil (O) 15s 1-15s
Interval2Gas (S) 2s
Interval2Oil (S) 2s
x x
x x x
x
Sets the minimum time the LMV5 stays in phase 34 on startups after a n
ormal shutdown.
Time will be longer if PrepurgeTmeGas(Oil) is set larger than PrepurgePt1Gas(Oil) +
PrepurgePt3Gas(Oil) . Setting has no effect on startups after a safety shutdown. If an Aux3
actuator is used, phase 34 is the time when the air actuator / VSD are at purge position and
the Aux3 actuator is also at purge position.
This defines the time the ignition transformer (OUTPUT X4-02.3) alone is energized before
the pilot valve (OUTPUT X9-01.2) or main valves (for direct spark fuel trains) become
energized. Sets the length of phase 38.
0.2s-63min
0.2s-63min
0.2s
0.2s
Params & Display>
BurnerControl>
Times>
TimesStartup1
Params & Display>
BurnerControl>
Times>
TimesStartup1
0.2-63s
0.2-630s
Params & Display>
BurnerControl>
Times>
TimesStartup2
Sets the maximum allowable time for SafetyTme1Gas(Oil) and SafetyTme2Gas(Oil) above.
x
When a fuel train with a pilot is used, this defines the overlap of the pilot (OUTPUT X9-01.2)
and the main fuel valves. After this time expires the pilot is de-energized if continuous pilot
is not selected. Shorter times are more safe. No effect for fuel trains having direct spark
ignition of main fuel. This time is also known as TSA2. Sets the length of phase 50.
Defines the main flame stabilizing period at ignition position before modulation. This time
begins after SafetyTme2Gas(Oil) expires. During this period, only the main fuel valves are
open. The pilot valve is de-energized unless continuous pilot is selected. No effect for fuel
trains having direct spark ignition of main fuel. Sets the length of phase 52.
Sets the time the LMV5 stays in phase 30 on startups after a normal shutdown. Setting has
no effect on startups after a safety shutdown. If an Aux3 actuator is used, phase 30 is the
time when the air actuator / VSD are at purge position and the Aux3 actuator is at home
position.
When a fuel train with a pilot is used, this setting defines the overlap of the spark (OUTPUT
X4-02.3) and the pilot valve (OUTPUT X9-01.2). After this time expires, spark is de-energized
but the PV remains open if a flame is present. If a flame is not sensed, a lockout occurs. If
directly spark igniting the main fuel, this defines the overlap of the spark and the main fuel
valves. This time is also known as TSA1. Sets the length of phases 40-42.
When a fuel train is selected that has a pilot, this setting defines the pilot stabilizing period.
This time begins after SafetyTme1Gas(Oil ) expires. During this period, only the pilot valve is
open. The spark is de-energized. If directly spark igniting the main fuel, this defines the main
stabilizing period. Sets the length of phase 44.
x x
SCC Inc. Page 8 Section 3
HOME
HOME
P - LIST

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals