SuggestedRatioControlCurveCommissioning
1. Theprocedurebelowassumesthefollowing:
a. PrerequisitesforBasicLMV51systemsorLMV52systems(fromabove)aremet.
b. ProcedureforConfiguring(Parameterizationof)anLMV5hasbeendone(fromabove).
c. ThisisafirsttimecommissioningoftheLMV5andthecombustioncontrolcurveisblank
(nopointsentered).
d. Theburnerhasbeenlitoff,andisatignitionposition.
e. Acalibratedstackgasanalyzerissamplingthestac
kgasandcanread%O
2
andppmCO.
f. Theboilerhasbeenwarmeduptooperatingtemperature/pressure.
2. Ifactivated,setparameterProgramStoptodeactivated.Thiswillpermittheratiocontrolcurve
tobecommissioned.Theratiocontrolcurvecanbefoundunderthemenu:
Params&Display>RatioControl>GasSettings>CurveParams
3. GotoPoint1.Point1isautomaticallysettoignitionpositionvalues.WhenPoint1isentered,
theAZLwillpromptto“change”or“delete”thepoint.“Change”shouldbeselected.Next,the
AZLwillpromptfor“Followed”or“Notfollowed”.“Followed”shouldbeselected.Allactuators
and / or VSD that have been activated should show up on this screen.If more than one Aux
actuator or VSD are activated, the screen may need to be scrolled down to show the other
actuators.IfanO
2
sensorisbeingusedandisactivated,theO
2
readingwillalsobedisplayed.
NOTE:Usingthe“Notfollowed”optionispossiblebutnotrecommendedformostsituations
sincetheresultsofchangingtheactuatorpositionsin“Notfollowed”modecannotbeseen
realtimeonacombustionanalyzer.When“Followed”isselected,acarat(>)isshownwhen
theactuators/VSDaremovingtothedisplayedposition.Acolon(:)isshownwhenthe
indicatedpositionsarereached.Apound(#)isshownwh
entheAux3FGRactuatorisbeing
heldatpositionduetoatimeortemperaturebasedFGRhold.
4. If the low fire point is not known (maximum burner turndown), adjust the Point 1 actuator
positions until maximum safe burner turndown is achieved.Record the fuel flow.If the fuel
flowisnotavailable,burnerheadpressurecanbeusedasalastresort.
Figure45:Point1ontheRatioControlCurve
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals