TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section4 Page16 SCCInc.
3. Ensureburnerswitchisoff.IftheLMV5isnotyetpowered,turnonthepowertotheLMV5.
4. Atthispoint,allsafetyinterlocksthatcanbecheckedshouldbecheckedinasafemanner.This
includesbutisnotlimitedto:lowwatercutoffs,hightemperatureswitches,highgaspressure
switch,lowgaspressureswitch,proofofclosure(POC),etc.
5. Later in the procedure
when the burner is running, the rest of the safety interlocks must be
checkedinasafemanner.Thisincludesbutisnotlimitedto:Airpressureswitches,highsteam
pressurelimits,draftswitches,etc.
6. SetparameterProgramStoptoInterva
l1,Phase44.Thiswillstoptheburnerfromprogressing
pastlightingthepilot.Thisparametercanbefoundunderthefollowingmenupath:
Params&Display>RatioControl>ProgramStop
7. Turn on the burner switch. The burner should drive to prepurge (Phase 24), drive to ignition
(Phase38),light
thepilot,andstopinpilotstabilization(Phase44).Ifthepilotdoesnotlighton
anewinstallation,therecouldbeairinthegasline.Bleedtheairinasafemannerifnecessary
andattempttorelightthepilot.
8. Oncethepilotislit,tunethepilotbyadjustingtheignitionpositionoftheair
actuatorand/or
adjustingthepilotgaspressureregulator,ifnecessary.Pilotflameshouldbestableandreturna
flamesignalof85%orgreater.Ignitionpositionscanbeadjustedatthistimeusingthefollowing
menupath:
Params&Display>RatioControl>GasSettings>SpecialPositions>IgnitionPos
9. Once a satisfactory
pilot flame is established, set ProgramStop to Interval 2, Phase 52.The
burnershouldopenthe mainfuel(gas)valvesandattempttolightthemainflame.TheLMV5
shouldshowaflamefailuresincethema
nualmainfuel(gas)valveisclosed.
10. Ifaflame failure does occur,proceedto reset theLMV5andopen the manualmain fuel (gas)
valve.Theburnershouldonceagainproceedthroughthestartupsequence,lightthepilotand
thenattempttolightthemainflame.
11. If the main flame lights, adjust the igniti
on position of the gas valve to achieve a safe main
flame.Atthistime,acalibratedstackgasanalyzershouldbeinsertedintothestackandusedto
evaluate combustion.If the main flame fails to light, the ignition position of the firing rate
control valve and / or the gas pressure regulator may need to be adjusted to achieve a
combustiblemixtureattheignitionposition. Afterthecomb
ustionhasbeenverifiedtobesafe
withananalyzer,ProgramStopcanbeleftatInterval2,Phase52forboiloutorboilerwarming
ifrequired.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals