LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page7 Section6
TheO
2
RatioControlCurvereflectsthe%O
2
thatresultedfromsettingtheFuelAirRatioControlCurve.
TheO
2
ControlCurveisthetargetfortheO
2
trimsystemwhenitisactivated.Whentheburneris
transitionedfromtheO
2
RatioControlCurvetotheO
2
ControlCurvebyincreasingtheStandardized
Value,theLambdaFactorwillbelearnedandrecordedatthatspecificpoint.Alargergapbetweenthe
O
2
RatioControlCurveandtheO
2
ControlCurvewillgivetheLMV52thebestopportunitytolearnthe
LambdaFactoroftheburner,andthusyieldthebestprecontrolwhentheburnerismodulating.Agap
of1%O
2
ormoreisideal,anditistypicallyachievableonnozzlemixingburnerswithnoorlow
percentagesofFGR.A1%gapistypicallynotachievableonpremixmeshburnersoronnozzlemixing
burnersthatuseahighpercentageofFGR.Thisgapalsosetstheavailablequantityof"lean"trimforan
LMV52.240,andthatiswhytheminimumrecomm
endedgapforanLMV52.240is1%.TheLMV52.440
usesadifferentO
2
trimalgorithmforpremix,meshandhighpercentageFGRburnersandcandealwith
aminimumgapof0.5%.

O
2
TrimConfiguration(Parameterization)BeforeCommissioning
TheprocedurebelowassumesanLMV52withdefaultparametersfortheO2Contr/Alarmmenuandthe
O2Modulemenu.IftheLMV52ismountedtoaburner/boiler,theburner/boilerOEMmayhave
alreadychangedtheparametersfromthedefaultsettingandparameterizedtheLMV52forthe
application.ThisprocedurealsoassumesthatallO
2
trimcomponentsareinstalledandwiredcorrectly,
andthattheO
2
trimwillbecommissionedonnaturalgas.
Section3givesadetailedexplanationofalloftheparametersintheLMV52aswellashighlightsw hich
parametersmust beset(marked witha doubleasterisk **)andwhich parametersarefrequentlyused
(shaded).
Thisproceduregivesageneralguidelineofwhatparametersneedtobesetonbothatraditionalnozzle
mixingburnerwithlittle tonoFGR, andalsofor lowandultralow NOxburn
ersthat arepremixmesh
type or high percentage FGR.Every burner is different, so it is likely that every burner will need a
somewhatuniqueparametersettoruncorrectly.
1. LoginattheOEMpasswordlevel.Fromthefactory,theOEMpasswordforth
eLMV5is"START".
2. Ifnotdonesoalready,activatetheO
2
sensorusingthefollowingmenupath:
Params&Display>O2Module>Configuration>O2Sensor=QGO20
3. Ifbeingused,configuretheappropriatetemperaturesensorsforblowerinletairtemperatureand
stacktemperature.Thisisdonethroughthefollowingmenupath:
Params&Display>O2Module>Configuration>SupAirTempSe
ns
Params&Display>O2Module>Configuration>FlueGasTempSens
ParameterSupAirTempSensactivatesandconfigurestheblowerinletairtemperaturesensor.
ParameterFlueGasTempSensactivatesandconfiguresthestacktemperaturesensor.Optionsare
Ni1000orPt10002wiresensorsforbothinputs.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals