TechnicalInstructions LMVSeries
DocumentNo.LV5‐1000
Section4 Page22 SCCInc.
SuggestedLoadControlSetup
After theRatioControlCurve has been commissioned, the load controllershouldbesetup.The load
controller can be run in internal load control modes (uses PID inside LMV5) or external load control
modes(usesaremotePIDcontrolseparatefromtheLMV5).Thetablebelowoutlinesthedifferentload
controlmodesavailable.MostLMV5soperatewiththeinternalloadcontroller.
Label Description
LMV5
Setpoint
UponX62.1‐
X62.2Closure
ExtLCX5‐03
Externalloadcontrol,firingratefrom
3‐positioninput
N/A(firingratevia
3‐positioninputor
stagedinput)
Changeto
“IntLC”,setpoint
W1
Externalloadcontrol,
stagedoil
IntLC
Internalloadcontrol,setpointset
locallyonLMV5
W1/W2
Remainin
“IntLC”,change
tosetpointW2
IntLCBus
Internalloadcontrol,setpointfrom
Modbuscommand
W3
(Modbus)
Changeto
“IntLC”,setpoint
W1
IntLCX62
Internalloadcontrol,setpointfrom
analogsignalonterminalX62
Remotesetpoint
ExtLCX62
Externalloadcontrol,firingratefrom
analogsignalonterminalX62
N/A(firingratevia
X62)
ExtLCBus
Externalloadcontrol,firingratefrom
Modbuscommand
N/A(firingratevia
Modbus)
Note:Bump‐lesstransfer(LMV5willnotcycleoff)willoccurfrom“IntLC”toanyexternalloadcontrol
mode.Bump‐lesstransferwillalsooccurfromanyexternalloadcontrolmodeto“IntLC”providedthat
thepressureortemperatureisnotabovethecycle‐offlimit(SD_ModOff).
Figure4‐7:LMV51.1andLMV52LoadControllerModes