10-4: AZL5 Software Version Updates
This section covers all of the revisions t
hat were made to the AZL5 with each new software
release. The software version of any AZL5 module can be found using the following menu path:
Params & Display > AZL > SW Version
AZL5 Software Update: Version 0220 to 0250
The following updates were made with A
ZL5 software version 0250:
1. The software version of the flash memory has been changed from V02.20 to V02.50.
2. For the load controller inputs 1 / 2 / 4, the following new parameter names have been
assigned:
Inp1/2/4Selection → Sensor Select
Inp1/4BerEnd → MeasureRangePtNi
Inp2TempBerEnd → MRange TempSens
Inp2PressBerEnd → MRange PressSens
Inp3Config_I/U → Ext Inp X62 U/I
Inp3MinSetpoint → Ext MinSetpoint
Inp3MaxSetpoint → Ext MaxSetpoint
3. When reading fuel usage in liters, a blank has been introduced between the value and the
unit.
4. The transfer of parameter copies from new LMV5 controllers to the backup memory of the
AZL5 is prevented. Copying is not possible and a message is delivered.
5. The default settings of the following parameters have been changed:
PrepurgeTmeGas: 15 seconds
MaxTmeLowFire: 45 seconds
PostpurgePosAir: 15°
PostpurgePosAux1: 25°
PostpurgePosAux3: 25°
PostpurgePosAux3: 25°
SD_Stage1On: -2%
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals