LMVSeries TechnicalInstructions 
 LV5‐1000
SCCInc. Page49 Section3

13) Actuatorpositionischeckedby using oneofthreemethods.Themethoduseddependsupon the phaseofthesequence.
PositionRequiredtoProceedmeansthattheactuatorsmustachieveandholdacertainpositionforthesequencetoproceed.
DynamicPositionCheckingmeansthattheactuatorisevaluatedbyaī˜ƒā€œtimeanddistancefromtargetā€ī˜ƒalgorithm.Thefurther
theactuatorisawayfromitstargetposition,thelesstimetheactuatorispermittedtobeinthatposition.Run‐TimePosition
Checkingmeansthattheactuatorisexpectedtobeatacertainpointinacertainamountoftime(basedoffoftherun‐time
oftheactuator).

14) For direct spark oil fuel trains, spark (ignition) will occur during prepurge if parameter OilPumpCoupling is set to
MagnetcouplandparameterIgnOilPumpStartissettooninPh22.

15) IfparameterFGR‐PS/FCCissetforPSdeactStby,thestatusoftheFGRpressureswitchisnotcheckedinphase10or12.The
restofthesequenceisthesameassettingthisparametertoFGR‐PS.IfparameterFGR‐PS/FCCissetforPSVSD,inputX4‐
01.3mustbeenergizedanytime  theVSD speedishigherthanRotSpeedPSonandde ‐energizedanytimetheVSD speedis
lowerthanRotSpeedPSoff.

16) DependingonhowparameterHeavyOilDirStartisset,inputX6‐01.3hasvaryingsequences.Ifthisparameterissetforactiv
38/44,input X6‐01.3mustbeenergizedinphase44.Ifthisparameterissetfor38/44..62,inputX6‐01.3mustbeenergized
inphases44‐62.Ifthisparameterissetforact21..62,inputX6‐01.3mustbeenergizedinphases21‐62.Ifthisparameteris
setfordeactivated,energizinginputX6‐01.3hasnoeffect.

17) Inputs X5‐03.2 and X5‐03.3 have many functions depending on how parameter Config X5‐03 is set.The settings are as
follows:

LMV5x std ā€“ī˜ƒ If parameter LC_OptgMode is set to ExtLC X5‐03, energizing X5‐03.2 will decrease the firing rate, while
energizingX5‐03.3willincreasethefiringrate.
LMV2/3stdī˜ƒā€“ī˜ƒIfparameterLC_OptgModeissettoExtLC  X5‐03,energizingX5‐03.3willachievestage2oil,whileenergizing
X5‐03.2willachievestage3oil.
LMV2/3invī˜ƒā€“ī˜ƒIfparameterLC_OptgModeissettoExtLC X5‐03,energizingX5‐03.2willachievestage2oil,while energizing
X5‐03.3willachievestage3oil.


