LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page3 Section4
c. Whenactuatorisinstalledandcoupled,ensurethatallmountinghardwareistightened
adequately,andsomemethodofthreadlockingisemployedonthemountin ghardware
(exceptforthecouplinghardware).
d. Ensureenvironmentalconditions(temperature,vibration, moisture,etc.)arenot
exceeded.
3. Ensurethatallwiringispertheappli
cablewiringdiagramandalsomeetsapplicablelocaland
nationalcodes.Particularatten
tionshouldbepaidtothefollowing:
e. Ifastepdowncontroltransformeristhesourceof120VACpowerfortheLMV5,the
groundandneutralshouldbebonded(connected)onthetransformer.
f. Voltagesupplytoa120VACLMV5mustbebetween102and132VAC,4763Hz.
Waveformmu
stbeafullsinewave.
g. Thesmalltransformer(s)usedfortheLMV5(AGG5.210,typicallyblueorblack)mustbe
wiredandgrounded.SeeSection2(Wiring)formoredetails.Payattentiontopins3and
4onterminalSEK2andpropergrounding.IfmorethantwoSQM48andoneSQ
M45
actuatorsaremodulatedatthesametime,asecondtransformer(AGG5.210)willbe
required.
h. CANbuswire(AGG5.643)mustbeused towirebetweenactuators.Plain,shieldedcable
isnotadequateandisnotpermitted.
i. EnsurethatthelastdeviceandonlythelastdeviceontheCANbushasthetermination
jumperin
the“BusTermination”position.SeeSection2(Wiring)formoredetails.The
AZLhasbuiltintermination.
4. Fuel(gas)supply mustbeadequatetosupporthighfireoperationandfuel(gas)trainmustbe
sizedcorrectly.
j. Fuel(gas)pressurebeforethefiringratecontrolvalvemustbecorrect,stableand
repeatableatallfiringratesandmustnotvarywhenotherfuel(gas
)burningappliances
(otherboilersinthebuilding)arebeingoperated.
k. Thefu
el(gas)pressureregulatorontheburnerbeingcommissionedshouldnotbefully
openathighfireandsho
uldnotbebouncingofftheseatatlowfire.Fuelregulator
mustbesizedproperly,andhaveadequateturndowncapability.
5. AtemporarystackgasanalyzerthathasbeencalibratedandataminimumreadsO
2
(%)andCO
(ppm)mustbeusedforsettingcombustion.
6. Knowledgeofwhatfuelflowrepresentshighfireoftheburner/boilercombinationandalsothe
turndownoftheburner/boiler combination.Thiscantypicallybefoundontheburner/boiler
nameplate.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals