Page #162 background imageLoading...
Page #162 background image
TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section5 Page10SCCInc.
Thepurposeofthestandardization(calibration)procedureistoestablishtherelationshipbetweenthe
LMV52analogoutputsignal(420mA)andtheblowerspeed,asreadbythespeedsensorconnectedto
theLMV52.Thisisdonebyrecordingablowerspeedwith19.5mAappliedtotheVFD.Oncestarted,
basicstepsinthestandardizationareasfollows:
1. Theairdamperisopenedtoprepurgeposition.
2. Therun/stopdry
contactintheLMV52isclosed.
3. Ananalogsignalof19.5mAisappliedtotheVFD.
4. TheVFD/blowerrampuptospeed.Afterthespeedhasstabilized,theactualpeakRPMisrecorded
byth
eLMV52.
5. Theanalogsignalisreturnedtominimum(typically4mA).
6. Therun/stopdrycontactintheLMV52isopened.
7. Theairdamperisreturnedtohomeposition.
Atypicalstandardizationprocessfora2pole(~3600RPM)blowerisshowngraphicallyinFigure53.Ifa
standardizationwasperfo
rmedona4pole(~1800RPM)blower,theprocedurewouldbesimilarbutthe
blowerspeedachievedat19.5mAwouldbeapproximately1750RPM.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals