TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section6 Page10SCCInc.
NOTE:The%O
2
valuesreadanddisplayedbytheLMV52systemarealwaysonawetbasis(%O
2
wet).Mostifnotallexternalexhaustgasanalyzersreadanddisplay%O
2
andothergasesonadry
basis(%O
2
dry).AllO
2
curvesmustbecommissionedusing%O
2
wetvaluesasreadbytheLMV52.
TheexternalexhaustgasanalyzerisusedtoreadCO,NOx,andalsoservesasawaytodouble
checkthe%O
2
wetvalues.Figure611givestheapproximaterelationshipbetween%O
2
wetand
%O
2
dry.
4. MakesurethattheQGO20O
2
sensorhasbeenactivatedforatleast2hoursandisupto
temperature.ThisgivestheZirconiumcelltimetoheatsoakandalsotoburnoffanycontaminants.
Thetemperatureofthecellcanbecheckedifdesiredthroughthefollowingmenupath:
Params&Display>O2Module>ProcessData>QGOSensorTemp
5. Withtheburneroff(Phase12),setthefuelrichlimit(O2Alarmvalu
e)foreachpoint.Thiscanbe
donewiththeburneroffsincethesevalueshavealreadybeenfoundandrecordedduringRatio
ControlCurvecommissioning(seeabove).OnceintotheO2Alarmcurve,simplyenterinthe
recordedvalueforeachpointandsaveeachpoint.ToaccesstheO2Ala rm curve,usethefollowing
menupath:
Params&Di
splay>O2Contr/Alarm>GasSettings>O2Alarm>O2Alarm
6. Withtheburneroff(P
hase12),setthefuelleanlimit(O2MaxValue)basedonthevaluesthathave
alreadybeenfoundandrecordedforPoint1andPoint10durin
gRatioControlCurvecommissioning
(seeabove).Tosetthefuelleanlimit,usethefollowingmenupath:
Params&Display>O2Contr/Alarm>GasSettings>O2Alarm> O2MaxValue
7. IftheLMVxCurvesspreadsheetisnotbeingused,ta
ketherecordedO
2
Alarmvaluesandadd0.5%
foreachpoint.Takethe"saved"%O
2
fromtheRatioControlCurveandsubtract1.0%foreachpoint.
ThiswillprovideatargetbandforsettingtheO
2
ControlCurvepoints.Example:TheO
2
Alarmvalue
is2%.TheRatioControlCurvepoint"saved"is4%.Add0.5%totheO
2
Alarm=2.5%.Subtract1%
fromtheRatioControl=3%.Forthispoint,thetargetfortheO
2
Controlisbetween2.5%and3%.
8. Whenitissafetodosoandwhenthereisadequateloadavailable,starttheburner/boilerandletit
warmuptooperatingtemperature.
9. AccesstheO
2
RatioControlCurveandtheO
2
ControlCurveusingthefollowingmenupath:
Params&Display>O2Contr/Alarm>GasSettings>O2Control
10. OncetheO
2
ControlCurveisentered,Point2shouldbedisplayed.PressingEnteragainshoulddrive
theburnertoPoint2ifitisnotalreadythere.WhentheburnerisdrivingtoPoint2,acarat(>)will
bedisplayed.OncetheburnerisatPoint2,acolon(:)willbedisplayed.Iftheaux3actuatorisused
forFGRandFGRModeisnotsetfor“Aux3onCurve”,apound(#)indicatestheaux3ac
tuatorhas
notreleasedtothecurve.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals