Technical Instructions LMV Series
Document No. LV5-100
0
Section 9 Page 10 SCC Inc.
iv. Next, go to the “System LMV5x” dro
pdown menu and select “Init BU”. A window
will appear and the ACS450 will begin reading the parameters. This will take a
few minutes. After this is complete, a window will appear that asks for a .par file.
Select the .par file that contains the parameter set to be uploaded. This
parameter set (.par) will overwrite the parameter set on the LMV5 and will
determine the behavior of the LMV5. Be sure that the correct .par file is
selected.
11. Click on “Store in LMV”. This will start the upload process.
12. The following messages should appear on the “Restore PC > LMV” window. These
messages are (in order): “Function Succeeded”, “Transferring Parameters”, “Status = 1”, “Status
= 2”, “Status = 3”, and “Parameter Transfer Succeeded”. The upload process may take up to five
minutes to complete. Also, an alarm may occur during the upload. This alarm is normal, and is
to alert the technician that the new parameter set has been uploaded to the LMV5.
13. Once the “Parameter Transfer Succeeded” message is shown on the “Restore PC > LMV”
window, click on “Close”. The alarm resulting from the upload can also be reset at this time.
The upload is now complete.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals