EasyManuals Logo

Siemens LMV5 Series Technical Instructions

Siemens LMV5 Series
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
LMV Series Technical Instructions
Document No. LV5-10
00
SCC Inc. Page 27 Section 1
1-4: Important Safety Notes
The LMV5 is a safety d
evice. Under no circumstances should the unit be modified or
opened. SCC Inc. will not assume responsibility for damage resulting from unauthorized
modification of the unit.
After commissioning, and after each service visit, the flue gas values should be checked
across the firing range.
All activities (mounting, installation, service work, etc.) must be performed by qualified
staff.
Before performing any work in the connection area of the LMV5, disconnect the unit
from the main supply (all-polar disconnection).
Protection against electrical shock hazard on the LMV5 and all other connected
electrical components must be ensured through good wiring and grounding practices.
Fall or shock can adversely affect the safety functions of an LMV5. Such units must not
be put into operation, even if they do not exhibit any apparent damage.
The coupling that is used between the actuator and the driven valve / damper is safety
related, and must be of a robust and flexible design. Should this coupling fail during
operation, the LMV5 will no longer have control of the burner’s combustion, bringing
about a hazardous condition.
Condensation and the entry of water into the unit must be avoided.
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals