Configuring the system
2.4 Configuring the SITOP UPS module for use with the PCU Base Software
PCU-Basesoftware (IM8)
Commissioning Manual, 02/2014, 6FC5397-1DP40-4BA0
71
“Fixed buffer time” mode
In this mode, the UPS module always buffers for the pre-selected, fixed period of time. It is
not possible to synchronize the UPS module with the operating system shutdown.
Required settings on the UPS module
On - Off
1
+2V
Cut-in threshold
+22V fixed
2
+1V
3
+0.5V
4
+1V
End-of-charge voltage
+ 26.3V fixed
5
+1V
6
+0.5V
7
+0.2V
8
+0.2V
9
+0.1V
10
0.35A / 0.7A Charging current