16.8.2 Setting interface parameters
Procedure
1. Select the "Start-up" operating area.
2. Press the "System data" softkey.
3. Press the ">>" and "Archive" softkeys.
4. Select the "RS-232-C settings" softkey.
The "Interface: RS-232-C" window is opened and the interface set‐
tings are displayed.
5. Press the "Details" softkey if you wish to view and process addi‐
tional settings for the interface.
RS-232-C settings
Parameter Meaning
Protocol The following protocol is supported for transfer via the RS-232-C:
RTS/CTS
Transfer It is also possible to use a secure protocol for data transfer (ZMODEM
protocol).
Normal (default setting)
Secure
For the selected interface, secure data transfer is set in conjunction
with handshake RTS/CTS.
Baud rate Transfer rate: The baud rate that can be used depends on the connected
device, the cable length and the general electrical conditions.
19200 (default setting, maximum baud rate for NCU (Linux))
115200 (maximum baud rate for PC/PCU (Windows))
Archive format
Punched tape
Binary format (PC format)
RS-232-C settings (details)
Interface
COM1
COM2 (only relevant for SINUMERIK Operate on PC)
Data backup
16.8 Serial interface (V24 / RS232)
SINUMERIK Operate (IM9)
Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1 367

Table of Contents

Other manuals for Siemens MCP 398C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MCP 398C and is the answer not in the manual?

Siemens MCP 398C Specifications

General IconGeneral
BrandSiemens
ModelMCP 398C
CategoryControl Systems
LanguageEnglish

Related product manuals