Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
136 Manual, 02/2008, A5E01168664B-04
INVERT CT POLARITY Inversion of the direction of current flow
ON/OFF switch:
ON / OFF.
OFF: SENTRON PAC3200 interprets the direction
of current flow in accordance with the wiring.
On: Direction of current flow is inverted.
SENTRON PAC3200 interprets the direction of current
flow opposite to the wiring.
Default:
OFF
9.2.5 Power demand
Device settings for acquiring the power demand.
Call: "SETTINGS > POWER DEMAND."
Figure 9-7 "POWER DEMAND" device setting
Power demand
TIME INTERVAL Time interval in minutes
Range: 1 to 60 min.
Default: 15 min.
SYNC. VIA BUS Synchronization via bus
Radio button:
ON / OFF.
Default:
OFF.
SYNC. VIA DIG.INPUT Synchronization via digital input
Radio button:
ON / OFF.
Default:
OFF.
If this option is activated, the "ACTION" field in the "DIGITAL
INPUT" device setting is set to "DEMAND SYNC". See the
chapter "Integrated I/O - DIGITAL INPUT".
See also
Integrated I/O (Page 137)