SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
157
Technical data
11
11.1 Technical data
Device configuration
1 slot for optional expansion module
1 optically isolated digital input
1 optically isolated digital output
1 Ethernet interface, RJ45 socket for connecting to the PC or network
Measuring inputs
Only for connection to AC voltage systems
Frequency of the relative fundamental 50/60 Hz
Set automatically
Measurement rate
Energy Continuous (zero blind measuring)
Current, voltage Continuous
Values on the display refreshed at least once per second
Waveform Sine or distorted
AC voltage input
Device with multi-range power supply
Phase-to-neutral voltage U
L-N
Phase-to-phase voltage U
L-L
3~ 400 V AC (+ 20 %), max. 347 V for UL
3~ 690 V AC (+ 20 %), max. 600 V for UL
Device with extra-low voltage power supply
Phase-to-neutral voltage U
L-N
Phase-to-phase voltage U
L-L
3~ 289 V AC (+ 20 %)
3~ 500 V AC (+ 20 %)
Minimum input voltage V
ph-n
3~ 40 V AC
Measuring category (in accordance with IEC/UL 61010 Part 1)
Input voltage V
I
V
I
to 230 V (V
ph-n
) CAT III
V
I
to 400 V (V
ph-ph
) CAT III
V
I
to 289 V (V
ph-n
) CAT III
V
I
to 500 V (V
ph-ph
) CAT III