3.9 Ethernet port
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
51
Offset Number of
registers
Name Unit Format Value range Access
32 = P_SUM
33 = VAR_SUM
34 = PF_SUM
35 = V_BAL
36 = I_BAL
50073 2 Value - float - RW
0 = greater than 50075 2 Modus ≥ / < - unsigned long
1 = less than
RW
Table 3-17 Settings parameter for limit value 1
Offset Number of
registers
Name Unit Format Value range Access
0 = OFF 50077 2 ON/OFF - unsigned long
1 = ON
RW
50079 2 Hysteresis % float 0.0 ... 20.0 RW
50081 2 Delay s unsigned long 0 ... 10 RW
0 = not used
1 = AND
50083 2 Operation in Limit Logic - unsigned long
2 = OR
RW
0 = V_L1
1 = V_L2
2 = V_L3
3 = V_L12
4 = V_L23
5 = V_L31
6 = I_L1
7 = I_L2
8 = I_L3
9 = VA_L1
10 = VA_L2
11 = VA_L3
12 = P_L1
13 = P_L2
14 = P_L3
15 = VAR_L1
16 = VAR_L2
17 = VAR_L3
18 = PF_L1
19 = PF_L2
50085 2 Source - unsigned long
20 = PF_L3
RW