Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
149
NOTICE
Access protection is switched off
Resetting to the factory defaults deactivates device protection. Password protection is
switched off. The password is set to the value "0000".
NOTICE
Counter - Reset
Resetting to the factory defaults has the effect of resetting all counters!
COMMUNICATION PARAM. Resets the entered TCP/IP address to:
0.0.0.0
EXECUTE Reset function. Resets the selected value
groups.
See also
Limits (Page 34)
9.2.10 PAC PROFIBUS DP expansion module
If the PAC PROFIBUS DP expansion module is plugged in , the device setting
"PROFIBUS MODULE" is executed in the "SETTINGS" menu.
Call: "SETTINGS > PROFIBUS MODULE".
PROFIBUS ADDRESS PROFIBUS address number of the device
Range: 0-126