3.1 Features
SENTRON PAC3200
20 Manual, 02/2008, A5E01168664B-04
Device versions
The device is available in the following versions:
Table 3-1 Device versions
SENTRON PAC3200 Power Monitoring Device
Order No. Description
7KM2112-0BA00-2AA0 SENTRON PAC3200 with multi-range power supply with ring lug terminals
7KM2112-0BA00-3AA0 SENTRON PAC3200 with multi-range power supply with screw terminals
7KM2111-1BA00-3AA0 SENTRON PAC3200 with extra-low voltage power supply with screw terminals
Measurement
Derivation of more than 50 measured variables from the basic measured variables with
maximum and minimum values (slave pointer function), as well as mean values for
phase-to-neutral voltages, phase-to-phase voltages and currents. The minimum and
maximum values are indicated in addition to the mean values.
With the multi-range power supply, the SENTRON PAC3200 can be connected direct to
690 V (max. 600 V for UL) industrial systems (measuring category III, pollution degree 2).
Higher voltages using voltage transformers.
With the extra-low voltage power supply, the SENTRON PAC3200 can be connected
direct to systems up to 500 V.
For current transformers x/1 A and x/5 A. Conversion ratio and current direction
programmable.
Can be used in 2-, 3- and 4-wire systems. Suitable for TN, TT and IT systems.
High measuring accuracy: 0.5% of the measured value for energy.
Counters and power demand
A total of 10 energy counters capture active energy, reactive energy, apparent energy for
off-peak and on-peak, import and export.
Calculation and storage of the last demand period mean value for active power and
reactive power for simple generation of load profiles using software. Programmable
demand period from 1 to 60 mins.
Configurable universal counter for counting limit violations and status changes at the
digital input or output, or for indicating the active power or reactive power of a connected
pulse encoder, e.g. S0 interface.
Working hours counter for monitoring the runtime of a connected load.