3.1 Features
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
21
Monitoring functions
Monitoring of 6 limit values. The limit values can be combined according to logic
AND/OR. A group message that indicates the violation of at least one limit value can be
generated using an OR operation.
Phase sequence monitor.
Status monitoring of the digital input.
Monitoring the operating status of the SENTRON PAC3200.
Displays and controls
Large backlit graphics LC display for optimal readability even from a distance.
Menu-driven parameterization and operation with plaintext display.
Choice of output language for menu and text displays.
Phase labels selectable (L1, L2, L3 <=> a, b, c).
Power supply
AC/DC multi-range power supply:
Supply by 95 to 240 V AC ±10 % / 50 / 60 Hz or
110 to 340 V DC ±10 %.
Extra-low voltage DC power supply:
Supply by 24 V, 48 V and 60 V DC ±10 % or
22 to 65 V DC ±10 %.
Installation format
Panel-mounting format 96 x 96 mm.
Only 51-mm installation depth without expansion module, 73-mm installation depth with
expansion module. The interface connector is plugged into the expansion module on the
side and thus does not increase the installation depth.
Interface
Integrated Ethernet interface.
Expandable with optional expansion module (e.g. PAC PROFIBUS DP Expansion
Module).
Expandable with optional expansion module (e.g. PAC RS485 Expansion Module).