Description
3.3 Measured variables
SENTRON PAC3200
26 Manual, 02/2008, A5E01168664B-04
Display of the measured variables depending on the connection type
The total extent of representable measured variables is restricted by the method of
connecting the device.
A measured value that cannot be indicated because of the connection method is shown on
the display by means of a broken line "----".
Figure 3-2 Display of the measured voltage in the case of connection type 3P4W
Figure 3-3 Display of the measured voltage in the case of connection type 1P2W
The table below, "Display of the measured values depending on the connection type", shows
which measured values can be represented depending on the connection type.
Table 3-4 Display of the measured variables depending on the connection type
Connection type
Measured variable
3P4W 3P3W 3P4WB 3P3WB 1P2W
Voltage a-n ✓ ✓ ✓
Voltage b-n ✓
Voltage c-n ✓
Average Voltage
a-n, b-n, c-n
✓
Voltage a-b ✓ ✓ ✓
Voltage b-c ✓ ✓ ✓
Voltage c-a ✓ ✓ ✓
Average Voltage
a-b,b-c ,c-a
✓ ✓ ✓
Current a ✓ ✓ ✓ ✓ ✓
Current b ✓ ✓
Current c ✓ ✓
Average Current a, b, c ✓ ✓
Apparent Power a ✓ ✓ ✓
Apparent Power b ✓
Apparent Power c ✓