EasyManua.ls Logo

Siemens SENTRON PAC3200 - Modbus Command Parameters; Table 3-26 Command Parameters

Siemens SENTRON PAC3200
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
3.9 Ethernet port
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
61
3.9.11 Modbus command parameters
Addressing the command parameters
You can use MODBUS function code 0x06 on the command parameters.
Table 3-26 Command parameters
Offset Number
of
registers
Name Unit Format Value range from ... to Access
60002 1 Reset maximum values - unsigned short 0 W
60003 1 Reset minimum values - unsigned short 0 W
0 = All
1 = Active Energy
Import Tariff 1
2 = Active Energy
Import Tariff 2
3 = Active Energy
Export Tariff 1
4 = Active Energy
Export Tariff 2
5 = Reactive Energy
Import Tariff 1
6 = Reactive Energy
Import Tariff 2
7 = Reactive Energy
Export Tariff 1
8 = Reactive Energy
Export Tariff 2
9 = Apparent
Energy Tariff 1
60004 1 Reset energy counter - unsigned short
10 = Apparent
Energy Tariff 2
W
60005 1 Synchronization of the
demand period
Min. unsigned short 1 ... 60 W
0 = High tariff 60006 1 Switching tariff - unsigned short
1 = Low tariff
W
60007 1 Acknowledge the diagnostics
bit
1)
(cf. stored bits in
unsigned long beginning
offset 205)
- unsigned short 0 ... ffffh W
0 = output 0 OFF 60008 1 Switching outputs (if
parameterized)
- unsigned short
1 = output 0 ON
W

Table of Contents

Other manuals for Siemens SENTRON PAC3200

Related product manuals