9.2 Parameterizing the operator interface
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
137
9.2.6 Integrated I/O
Device settings for using the digital input and output.
Call: "SETTINGS > INTEGRATED I/O".
Figure 9-8 "INTEGRATED I/O" device setting
DIGITAL OUTPUT
Figure 9-9 "DIGITAL OUTPUT" device setting
ACTION Method of using the digital output:
OFF: The digital output is switched off.
DEVICE ON: The digital output is switched on.
REMOTE OUTPUT. The digital output is controlled by remote
access, e.g. SEAbus, SEAbus TCP,
PROFIBUS DP, Modbus RTU,
Modbus TCP.
ROTATION: The digital output is switched on by a left-
rotating electrical field and remains active
while the direction of rotation of the field
remains unchanged.
LIM.VIOLATION: The digital output is switched on by a limit
violation and remains active while the limit
violation prevails.
The field "DIGITAL OUTPUT > SOURCE"
selects the limit to be monitored. The
definition of the limit is stored in
"ADVANCED > LIMITS".