Description
3.9 Ethernet port
SENTRON PAC3200
62 Manual, 02/2008, A5E01168664B-04
Offset Number
of
registers
Name Unit Format Value range from ... to Access
60009 1 Switching command for vector
group
- unsigned short High 0 ... 99, Low 0 ... 1
High byte group
assignment
Low byte 1 = ON,
0 = OFF
W
65300 1 Activation of a changed IP
configuration/ Ethernet
configuration
- unsigned short 0 W
1) The MODBUS master must acknowledge these diagnostics bits.
See also
Modbus measured variables with the function codes 0x03 and 0x04 (Page 40)
3.9.12 MODBUS standard device identification with the function code 0x2B
Addressing the MODBUS standard device identification
You can use MODBUS function code 0x2B on these device identification parameters.
Table 3-27 MODBUS standard device identification parameters
Object ID Name Format Access
OID 0 Manufacturer String R
OID 1 Manufacturer device name String R
OID 2 Firmware version / bootloader version String R
See also
Modbus measured variables with the function codes 0x03 and 0x04 (Page 40)