Description
3.9 Ethernet port
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
39
F3 runs through the digits of the value from left to right.
F2
increments the value at the selected digit. The highest value of the available set of
values is followed again by the lowest.
Figure 3-9 Enter IP address
F4 saves the set IP ADDRESS and returns to display mode.
Change to the next line SUBNET with F3
, and press F4 .
Repeat the procedure described for the settings SUBNET and GATEWAY.
Figure 3-10 Typical display with entered values
Switching from the SEAbus TCP protocol to MODBUS TCP
Use F3 to change to the "PROTOCOL" entry
Press F4
.
Switch the protocol from "SEAbus TCP" to "MODBUS TCP" with F2
Figure 3-11 Switching the protocol to MODBUS TCP
Confirm your selection with F4 .
F1
terminates the input and a message window prompts you to restart.
Figure 3-12 Restart prompt
F4 carries out a restart - your settings become effective.