Operation planning
4.1 Operation planning
SENTRON PAC3200
66 Manual, 02/2008, A5E01168664B-04
Installation space and ventilation
Sufficient clearance must be maintained between the device and neighboring components in
order to comply with the permissible operating temperature. You can find dimension
specifications in the "Dimension drawings" chapter.
Plan additional space for:
Ventilation
Wiring
RJ45 plug connector and cable feed on the top of the device
Optionally connectable expansion module on the rear of the device, including connector
and cable feed
CAUTION
Ensure ventilation
Please ensure that the ventilation slots of the housing are not obstructed. The wiring,
cable feed or other components must not obstruct ventilation.
Environmental conditions
Only use the SENTRON PAC3200 device where the environmental conditions permit its
operation:
Temperature range
Operating temperature range
- 10 °C through + 55 °C
Storage temperature range
- 25 °C through + 70 °C
Relative humidity 95% at 25°C without condensation (normal
conditions)
Operating altitude above sea level Up to 2000 m
Degree of pollution 2
Degree of protection according to IEC 60529
Front
IP65
Rear
IP20, NEMA 1A
Temperature compensation
To avoid condensation, the device must be stored at the operating location for at least 2
hours before power is connected.
See also
Dimension drawings (Page 167)