Operation
7.1 Operating modes of the transfer switching equipment
104 Manual, 08/2017, L1V30368969104A-02
The 3KC4 and 3KC8 transfer switching equipment can be secured in position O (OFF) using
a padlock. This can effectively prevent operation of the transfer switching equipment by
unauthorized persons.
Up to 3 padlocks with diameters between 4 and 8 mm can be attached on the motor operator
assembly.
Padlocking mode
● blocks remote control using inputs (312-317) as well as automatic mode of the electronic
module (3KC8 transfer switching equipment only),
● prevents attachment of the handle.
The transfer switching equipment can only be locked under the following conditions:
• The transfer switching equipment is in "manual operation" mode
• The handle is removed.
1. Remove the handle if applicable
2. Turn the switch on the motor operator from the "Auto" position to the "Manual" position to
change from remote / automatic mode (3KC8 transfer switching equipment only) to
manual operation.
Figure 7-7 Setting padlocking mode
3. Pull the locking device out of the motor operator and secure it with a padlock.