Operation
7.1 Operating modes of the transfer switching equipment
Manual, 08/2017, L1V30368969104A-02
105
7.1.4
Automatic mode (3KC8 only)
In automatic mode, the 3KC8 transfer switching equipment is controlled by the automatic
system of the electronic module. This switches the transfer switching equipment to the
different switch positions depending on source availability.
To enable a transfer, the electronic module must be programmed according to source
requirements. Programming is described in the section titled Automatic mode - programming
of the electronic module (3KC8 only) (Page 132).
Automatic mode
activates the controller and automatic mode of the electronic module,
prevents padlocking mode,
prevents attaching of the handle.
Setting automatic mode
1. Turn the switch on the motor operator from the "Manual" position to the "Auto" position to
change from manual operation to automatic mode.
Figure 7-8 Activating automatic mode
The "Power" LED on the motor operator shows a continuous green light.
The "Auto" LED on the electronic module shows a continuous green light or flashes green
(depending on the default with regard to the timer).
The "Ready" LED on the electronic module shows a continuous green light.
Note
You
cannot
activate remote mode in the following cases:
The handle is located in the assembly.
The transfer switching equipment is locked using a padlock (padlocking mode).