Commissioning
10.3 Commissioning the ET 200SP on PROFIBUS DP
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
205
To commission the ET 200SP distributed I/O system as a DP master on PROFIBUS DP, we
recommend the following procedure:
Table 10- 4 Procedure for commissioning the ET 200SP as a DP master on the PROFIBUS DP
Installing ET 200SP (with CPU and CM DP)
Section Installation (Page 54)
2 Connecting ET 200SP
• Supply voltages
• PROFIBUS DP
• Sensors and actuators
Section Wiring (Page 75)
3 Inserting a SIMATIC memory card in the DP
master (CPU)
Section Removing/inserting a
SIMATIC memory card on the CPU
4 Configuring DP master (including PROFIBUS
address)
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
5 Switching on supply voltages for DP master CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
Switching on supply voltages for DP slaves
Documentation of the DP slave
Download configuration to the DP master
8 Switching DP master to RUN CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
9 Checking LEDs CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
10 Testing inputs and outputs The following functions are helpful:
Monitoring and modifying tags,
testing with program status, forc-
ing, controlling the outputs. See
section Test functions and elimi-
nating problems (Page 259)