Commissioning
10.9 Identification and maintenance data
Distributed I/O system
222 System Manual, 12/2016, A5E03576849-AG
Procedure for reading I&M data by means of the user program
In order to read the I&M data of the modules in the user program, use the RDREC
instruction.
The data record structure for modules that are distributed and accessible via PROFINET IO/
PROFIBUS DP is described in the section Structure of the data record for I&M data
(Page 223).
Procedure for reading the I&M data using STEP 7
Requirements: There must be an online connection to the CPU/interface module.
Proceed as follows to read the I&M data via STEP 7:
1. In the project tree, under "Distributed I/O" select the IO device IM 155-6 PN ST (for
example).
2. Select
> IO device > Online & diagnostics > Identification & Maintenance
.
Procedure for input of maintenance data using STEP 7
STEP 7 assigns a default module name. You can enter the following information:
Plant designation (I&M1)
Location identifier (I&M1)
Installation date (I&M2)
Additional information (I&M3)
To enter maintenance data via STEP 7, follow these steps:
1. In the device view of the STEP 7 hardware network editor, select the interface module, for
example.
2. In the properties under "General", select the "Identification & Maintenance" area and
enter the data.
During the loading of the hardware configuration, the I&M data is also loaded.
Procedure for reading I&M data via the Web server
The procedure is described in detail in the Web server
(http://support.automation.siemens.com/WW/view/en/59193560) Function Manual.