System overview
2.3 How are SIMATIC Safety F-systems structured with ET 200SP?
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
23
Hardware and software requirements
ET 200SP fail-safe modules are supported by interface modules IM155-6PN BA, firmware
V3.2 or higher, IM155-6PN ST, firmware V1.1.1 or higher, IM155-6PN HF, firmware V2.0 or
higher, IM155-6PN HS firmware V4.0 or higher and IM155-6DP HF, firmware V1.0 or higher.
You require the STEP 7 Safety Advanced option package, V12 or higher including HSP 54,
for configuration and programming of the ET 200SP fail-safe modules with the SIMATIC
Safety fail-safe system.
You require the F-Configuration Pack V5.5 SP10 for configuration and programming of the
ET 200SP fail-safe modules with the Distributed Safety fail-safe system.
You require the F-Configuration Pack V5.5 SP12 for configuration and programming of the
ET 200SP fail-safe modules with the F/FH Systems fail-safe system.
ET 200SP fail-safe motor starters are supported by interface modules IM155-6PN BA,
firmware V3.2 or higher, IM155-6PN ST, firmware V3.1 or higher, IM155-6PN HF, firmware
V3.1 or higher and IM155-6DP HF firmware V3.0 or higher.
You require SIMATIC Step 7 V14 or higher for configuration and programming of ET 200SP
fail-safe motor starters. The F-Configuration Pack is not needed for configuration and
programming of the ET 200SP fail-safe motor starter.
Note
Configuration of
ET 200SP motor starters, SIMATIC Step 7 V13 or higher, is possible with a
G
SD file (GSDML).
Use in safety mode only
Safety mode is the F-I/O operating mode that allows safety-related communication using
safety frames.
Safety mode of motor starters is characterized by the fail-safe digital input (F-DI) and
availability of the 24 V power supply.
You can only use the ET 200SP fail-safe I/O modules in safety mode. They cannot be used
in non-fail-safe mode.