Wiring
5.6 Wiring rules
Distributed I/O system
88 System Manual, 12/2016, A5E03576849-AG
TWIN end sleeves for the cables of the I/O modules' push-in terminals
Due to the space required by TWIN end sleeves with 0.75 mm
2
cross-section, you must
ensure a correct angle for the cable arrangement when crimping the TWIN end sleeve so
that the cables are optimally arranged.
Cross-section of the terminal compartment
Crimping TWIN end sleeves at the correct angle
Figure 5-4 TWIN end sleeves
Wiring rules for motor starters
Wiring rules for ...
L1(L), L2(N), L3,
PE
T1, T2, T3, PE, 24 V DC, F-DI,
M
DI1 ... DI3, LC, M, 24 V
OUT
Connectable cross-sections for solid
cables
1 to 6 mm
2
0.5 to 2.5 mm
2
0.2 to 1.5 mm
2
AWG: 18 to 10
AWG: 20 to 12
AWG: 24 to 16
Connectable cross-
sections for flexible
cables
Without end
sleeve
1 to 6 mm
2
0.5 to 2.5 mm
2
0.2 to 1.5 mm
2
AWG: 18 to 10
AWG: 20 to 12
AWG: 24 to 16
With end sleeve
1 to 6 mm
2
0.5 to 2.5 mm
2
0.25 to 1.5 mm
2
AWG: 18 to 10
AWG: 20 to 12
AWG: 24 to 16
With end sleeve
(with plastic
sleeve)
1 to 4 mm
2
0.5 to 1.5 mm
2
0.25 to 0.75 mm
2
AWG: 18 to 11 AWG: 20 to 16 AWG: 24 to 18
Stripping length of the wires 15 mm 10 mm 8 mm
End sleeves according to DIN 46228
with plastic sleeve
15 mm long 10 mm long 8 mm long