Installing and connecting the device
3.2 Mounting the device
SIMATIC IPC347G
Operating Instructions, 10/2020, A5E50059993-AA
31
3.2 Mounting the device
3.2.1 Mounting types
Note
If the equipment is used in a manner not specified by the manufacture
, the protection
provided by the equipment might be impaired.
The device is approved for indoor operation only.
When the device is used in the area of Industrial Control Equipment in accordance with
UL61010-2-201, the device is classified as "Open equipment".
Open equipment must be installed within an enclosure which protects you from hazards,
including mechanical hazards, electrical shock and spread of fire.
Install the device only in one of the described permitted mounting positions.
For installation of control cabinet, observe the country-specific regulations.
Provide adequate volume in the switchgear cabinet for air circulation and heat transport.
Keep at least 10 cm between the device and the switchgear cabinet.
Do not cover the vent slots of the device.
Ensure that the maximum air intake temperature, measured 5 cm before the air intake
opening, does not exceed 40° C. The maximum air intake temperature must be accounted
for especially when sizing closed switchgear cabinets.
The minimum distance between the device and the housing is 10 cm on the air output
end.
Ensure that the installed device does not pose a danger, for example, hit someone by
falling over.
All the external circuit of the device must be SELV circuit.