Approvals
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
309
The device meets the requirements of the EC Directive:2004/108/EEC "Electromagnetic
Compatibility” (EMC directive).
Applied standards:
● EN 61000-6-4
Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission standard
for industrial environments
● EN 61000-6-2
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for
industrial environments
The device meets the requirements of the EU directive 2011/65/EC on the restriction of the
use of certain hazardous substances in electrical and electronic equipment.
Applied standard:
● EN 50581:2012
Applied standards:
● Underwriters Laboratories, Inc.: UL 508 Listed (Industrial Control Equipment)
● Canadian Standards Association: CSA C22.2 No. 142 (Process Control Equipment)
Report / UL file: E85972 (NRAG, NRAG7)
cULus Hazardous (Classified) Locations
Underwriters Laboratories, Inc.: CULUS Listed 7RA9 IND. CONT. EQ. FOR HAZ. LOC.
Approval for the device
Applied standards:
● ANSI ISA 12.12.01
● CSA C22.2 No. 213-M1987
APPROVED for Use in:
● Cl. 1, Div. 2, GP. A, B, C, D T4
● Cl. 1, Zone 2, GP. IIC T4
Ta: Refer to the temperature information on the type plate of the device
Report / UL file: E223122 (NRAG, NRAG7)
Note the conditions for the safe deployment of the device according to the section Notices on
use in hazardous areas according to UL HazLoc (Page 66).